Page 442 - Boiler_Operators_Handbook,_Second_Edition
P. 442

Controls                                                                                            427


                                                                        Thermometers and temperature transmitters are
                                                                    occasionally installed in such a manner that they’re use-
                                                                    less. The temperature sensing portion of the instrument
                                                                    must  be  in  the  process  fluid  where  it’s  flowing.  One
                                                                    measurement that is always a problem is boiler stack
                                                                    temperature. I’ve encountered situations where the
                                                                    stack thermometers had stems so short that they didn’t
                                                                    penetrate the stack. On others the thermometer bulb
                                                                    was located in a zone where the flue gas was idle, a stag-
                                                                    nant zone where the gas was much cooler than the flow-
                                                                    ing flue gas. Here’s one spot where modern technology
                                                                    has created some problems because the two common
                                                                    measures used for temperature detection, RTDs and
                                                                    thermocouples, are point instruments, they only sense
                                                                    temperature at one point.
                                                                        We used to have these wonderful capillary type
                                                                    temperature transmitter elements that allowed us to
                                                                    stretch the probe back and forth across the stack or
                                                                    boiler outlet several times in a pattern that insured we
                                                                    had an average reading of the gas temperature. The
                                                                    problem is they were filled with mercury. I wouldn’t
                                                                    recommend an RTD for stack temperature service
                                                                    because they can’t take high temperatures that can oc-
                 Figure 11-41. Steam and liquid transmitter piping  casionally occur in a stack.
                                                                        When doing it right I specify a multipoint ther-
               the transmitter below gas piping (especially for com-  mocouple with an element that spans the stack and has
               pressed air and, in some parts of the country, fuel gas)  several terminations in it along with several reference
               the arrangement shown for liquids should be used and  junctions outside the stack so it will provide an average
               a schedule prepared for regular draining of the dirt legs.  reading. I prefer a single point bi-metal thermometer for
               Otherwise, install it above the line so everything can  the local instrument because the large dial makes it easy
               drain away.                                          to read from floor or access platform level. I just make
                    Installation of oxygen analyzers and their sam-  certain the stem is long enough so it will always be in the
               pling locations has varied with the type of instrument  center of the gas flow. I have encountered stack thermom-
               over the years. The in-situ analyzers eliminate problems  eters with a bulb so short that the sensitive tip wasn’t in
               with sampling lines but introduced other problems. The  the stack. A boiler stack should have 3” to 4” of insulation
               analyzer has to be installed where it senses a representa-  and a nipple and coupling extending through to mount
               tive sample of the flue gas (that’s engineer for taking a  the transmitter. A standard 2-1/2” bulb is too short.
               reading of what’s really flowing). It also has to be where     With the possible exception of stack and air duct
               the wiring will not be overheated, and in a manner that  temperature measurements all thermometers and tem-
               ensures the reference gas isn’t contaminated. See the  perature transmitter elements should be installed in
               discussion under oxygen trim.                        thermowells. That way, if you do question an instru-
                    Some in-situ analyzers have been installed at the  ment’s accuracy you can remove it and have its calibra-
               furnace outlet which will work well on boilers with low  tion checked, or check it yourself if you have the right
               heat release rates. If the temperature of the flue gas at  equipment.
               the sampling point is above 1500°F then the gas will be     Stacks and air ducts may simply contain air at
               too hot to control its temperature and the analyzer will  ambient temperatures or be under negative pressure
               produce erroneous signals. I recommend installation of  so there is no hazard associated with removal of the
               the analyzer so the probe is centered in the upper third  thermal element and a thermowell isn’t necessary.
               of the smallest gas passage (in cross section) at the boiler  Sometimes, however, the well is essential to support
               outlet. If the boiler is equipped with an economizer or  the thermal element. Thermowells tend to slow the re-
               air heater it should be installed before that equipment.  sponse of the instrument to changes in temperature be-
   437   438   439   440   441   442   443   444   445   446   447