Page 199 - Boiler plant and distribution system optimization manual
P. 199

184                                                 Boiler Plant and Distribution System Optimization Manual


                     Example. Heavy rains have soaked the coal           does this reduce the boiler firing rate?
                     supply and surface moisture is over 15%,            (Ans. 5%)
                     how  will  this  change  the  capacity  and  ef-
                     ficiency  of  a  200,000  pph  (100  ton)  boiler?   h.   Power used in pumps and fans varies with
                     ____________                                        the cube of the rpm.
                     (Ans. efficiency will drop by 1.5%, capacity will   Note:  Tests  have  shown  that  power  reduction
                     drop by 3,000 pph or 1.5 tons/hr)                   may vary with the square of the rpm when a
                                                                         static head is involved.
                e.   A  10%  change  in  wood/bark  moisture
                     changes efficiency by 1.5%                          Example.  Estimate  the  power  demand  re-
                     Example. Moisture has changed from 30%              ductions  produced  by  the  following  rpm
                     to 60%, how will this change efficiency and         changes using the “cube” relationship.
                     output? ____________
                     (Ans. efficiency and capacity will drop by 4.5%)     Reduction of rpm to    90%    80%     50%
                                                                         Power Reduction         ——     ——     ——
                f.   A  10%  change  in  Bagasse  moisture  will
                     change efficiency by 3.0%.                          Ans.  (90% Cubed—73% of original power)
                     Example. A new system to dry bagasse is be-               (80% Cubed—51% of original power)
                     ing evaluated, it can reduce moisture from                (50% Cubed—12.5% of original power)
                     50% to 15%, how will this change efficiency
                     and capacity? ____________
                     (Ans. Efficiency and Capacity change by 10.5%.   REDUCING ExCESS AIR TO
                     Fuel savings if the original efficiency is 65% will   IMPROVE EFFICIENCY
                     be 14%)
                                                                         The purpose of this section is to show how
                g.   A  11°F  condensate  temperature  change  im-  changing excess air changes heat losses.
                     proves efficiency by 1%.
                     Example. Condensate temperature drops          1.   A Natural Gas boiler has a stack tempera-
                     from 195F [91C] to 160F [71C] during a cold         ture of 600F [316C]. What will the efficiency
                     period.  How  has  this  changed  system  effi-     increase and fuel savings be if the average
                     ciency? ____________                                excess air is reduced from 90% to 15% (CO
                                                                                                                    2
                     (Ans. 3.2%)                                         from 5.9% to 10.1%)?

                     Example. Condensate temperature suddenly            As found efficiency            73.8%
                     rises from 160F [71C] to 200F [93C], estimate       Net stack temperature
                     the amount of steam trap leakage if no make            600F-80F                    520F [271C]
                     up water is being used.                             CO                             5.9%
                                                                            2
                     (Ans. 3.6% of system load)
                                                                         Efficiency with reduced
                     Example.  High  pressure  feedwater  heater            excess air                  80.6%
                     temperature drops from 350F [177C] to 320F          Net stack temperature
                     [160], how will this change boiler firing rate?        600F-80F                    520F [271C]
                     (Ans . 2 . 7% more capacity will be needed to heat      CO 2                       10%
                     the feedwater)
                                                                             Fuel savings    ____%
                     Example. If an economizer raises the feed-          (Ans.: 8.4%)
                     water  temperature  55F  [13C],  how  much
   194   195   196   197   198   199   200   201   202   203   204