Page 297 - Boiler plant and distribution system optimization manual
P. 297

282                                                 Boiler Plant and Distribution System Optimization Manual


                remove dissolved gases from the boiler feed wa-     widely. A low pressure firetube boiler can usually
                ter. They are effective and oxygen can be reduced   tolerate higher feedwater hardness, with proper
                to trace levels; about .005 ppm. While deareators   chemical treatment, while virtually all impurities
                are efficient, traces of oxygen can cause a signifi-  must be removed from the water used with most
                cant amount of corrosion, so chemical treatment     modern high pressure watertube boilers.
                is also used.
                     While the deareator removes carbon dioxide
                from  the  feed  water,  bicarbonate  and  carbonate   WATER CARRYOVER IN STEAM
                alkalinity  in  the  boiler  will  produce  addition-
                al carbon dioxide. This will require some water          The  water  evaporated  to  produce  steam
                treatment in the boiler.                            should not contain any contaminating materials,
                     A deareator usually consists of a heating and   however there will be water droplets carried into
                deareating section.  The  storage section  of  these   steam due to several processes.
                units are often designed to hold about 10 minutes
                of rated capacity of boiler feed water.             MIST CARRYOVER
                     The water enters the deareator and is broken        A fine mist is developed as water boils. This
                into a spray or mist and scrubbed with steam to     process is illustrated in Figure 15.2. A bubble of
                force out the dissolved gasses.                     water  vapor  (steam)  reaches  the  water  surface
                     Steam and noncondensibles into the vent        and  bursts,  leaving  a  dent  in  the  water.  Liquid
                condensing section where the steam is condensed.    collapses in on the dent, with the center rising at
                The released gases are discharged to atmosphere     a faster rate than the edges. This results in a small
                through the vent outlet.                            droplets being tossed free of the boiler water sur-
                                                                    face. These droplets form a fine mist. This mist is
                Continuous Blowdown Heat Recovery                   removed to a great extent in the dry portion of the
                     The   continuous  blowdown,  sometimes         boiler. However, any mist that remains entrained
                called the surface or skimmer blowdown, is most     in the steam will have the same level of contami-
                effective in controlling the concentration in boiler   nation as the boiler water.
                water. Where continuous blowdown systems are
                used, the bottom blowdown is used for removal       Foaming Carryover
                of precipitated impurities, especially those which       The alkalinity, TDS and suspended solids can
                tend to settle in the lower parts of the boiler.    interact to create a foam in the boiler. A light foam
                     Heat exchangers can be used with the contin-
                uous blowdown to recover energy from the boiler
                water which is being expelled from the boiler.

                How pure must feedwater be?
                     Feedwater purity is a matter of both quan-
                tity of impurities and the nature of the impuri-
                ties. Some impurities such as hardness, iron and
                silica for example are more concern than sodium
                salts. The purity requirements for any feedwater
                depend on how much feedwater is used as well
                as what the particular boiler design is. Pressure,
                heat transfer rate and operating equipment on
                the system such as turbines have a lot to do with
                                                                    Figure 15.2—Mist  formation  in  boiler  water with
                feedwater purity.
                                                                    high impurity levels. The volume above the water is
                     Feedwater  purity  requirements  can  vary
                                                                    steam, steam bubble is shown for illustration.
   292   293   294   295   296   297   298   299   300   301   302