Page 451 - Chemical process engineering design and economics
P. 451

432                                                      Chapter 8

           and because Q = AQ VQ, the volumetric flow rate,

                  f(P,- 2)V  /2
                        P
           Q=   Cyl  ————    I                                            (8.7)
                  I     n    )

           which is a formula  used by valve manufacturers  to  size valves for incompressible
           fluids.  Because the valve coefficient,  Cy, contains the orifice  area, C is not a con-
                                                                  v
           stant  for  any particular  valve  but  varies  with  the  position  of  the  valve  stem  and
           hence the valve plug. The units used for Cy by valve manufacturers  are gal/min for
           flow rate and Ibp/in2 for pressure. Thus, Cy has units of gal-in/min-lbi;1'2
                 Sizing valves requires  calculating  Cy  for the  design  flow  rate  and then  se-
           lecting an appropriate valve from a manufacturer.  The valve coefficient  contained
           in  manufacturers'  catalog  is the  maximum  coefficient.  If the  valve  were  sized  at
           the normal operating flow rate, the system would then be out of control if an upset
           should occur.  To  avoid this, Chalfin  [9] recommends  sizing a control valve  for a
           flow rate that is 30% greater than the normal operating flow rate.
                The  designer,  to  insure  good  process  control,  specifies  the  pressure  drop
           across the valve. At low-pressure drops, the valve characteristic curve is distorted
           resulting in poor control. Boger [10]  and Moore [11]  discuss this effect.  The valve
           characteristic curve is a plot of the valve opening against flow rate. There are sev-
           eral  rules  of  thumb  in  the  engineering  literature  for  assigning  the pressure  drop
           across a control valve.  Sandier and Lukiewicz [29]  recommend a pressure drop of
           30 to 50% of the frictional pressure drop -  also called the dynamic pressure drop -
           in the system and a minimum of 5 to  10 psi (0.345 to 0.67 bar). Forman [12] states
           the assigned pressure  drop is not an arbitrary value like 5 psi (0.345 bar). He rec-
           ommends a pressure drop of 33%  of the frictional  pressure drop for a linear valve
           and  50%  for an equal-percentage valve  [12]. For  a valve that has a linear charac-
           teristic curve, the flow rate varies linearly with valve opening. For a valve that has
           an  equal-percentage  characteristic  curve,  the  flow  rate  varies  non-linearly  with
           valve  opening.  Power  consumption  increases  with  increasing  frictional  pressure
           drop. Thus, the assigned pressure drop should not be any larger than necessary for
           adequate control. Example 8.1 illustrates the procedure for valve sizing.
           Example 8.1 Valve Sizing______________________________


           What  size  valve  will  be  required  to  control  the  flow  rate  of  50  gal/min  (0.169
             3
           m /min) of brine (rj  =  1.2), if the frictional  pressure drop in the system, excluding
           the valve, is  15 psi (1.03 bar)?  Assume a linear valve.

           Q (design) =  1.3 (50) = 65 gal/min (0.246 nrVmin).






         Copyright © 2003 by Taylor & Francis Group LLC
   446   447   448   449   450   451   452   453   454   455   456