Page 487 - Construction Waterproofing Handbook
P. 487

LEAK INVESTIGATION AND DETECTION  13.3
                         suggests outside assistance is necessary and if emergency repairs are necessitated to pre-
                         vent further damage and related escalating costs associated with this damage.
                            The initial leak reports are usually not sufficient to immediately determine the cause
                         of leakage. It often takes further investigation, including inspections and testing, to pro-
                         vide sufficient knowledge for effective decisions on how to best make necessary repairs.
                         The original construction documents also can provide important clues to the leakage
                         cause(s).

                         Document review
                         Prior to the actual inspection, a thorough review of all available construction and as-built doc-
                         uments should be made, highlighting the general area of the leakage. Make note of any ques-
                         tionable termination and transition detailing of all envelope components. Determine the
                         barrier line (described in Chap. 10), and specifically note if it was properly “closed” and hence
                         ensuring that all individual components of the envelope are transitioned into the adjacent com-
                         ponent or system with watertight connections. If the original documents do not clearly detail
                         transition requirements, this should become an area for further visual field inspection.
                            A basic guide to the review of documents should include

                         1. Reviewing all individual envelope components. At the building elevation in question,
                            the as-built drawings should be used to determine each of the individual components
                            used in construction. Decide if any are likely contributors to the leakage that require
                            visual inspection in the field. For example glass is not a likely contributor, but precast
                            panels that have cracked can cause leakage. Highlight all individual waterproofing and
                            roofing systems used in the envelope construction. Make note of each of these systems
                            for field inspection. When reviewing these systems remember the 99% principle: that
                            99% of leakage is attributable to installation problems and not to actual waterproofing
                            or roofing system failures.
                         2. Determine the barrier line. Determine if the documents required a weathertight enve-
                            lope barrier or if there are areas of concern. Do the envelope transition barrier systems
                            to divertor systems function properly? Document all areas that require further study in
                            the field inspection.
                         3. Study termination and transition detailing. Keep in mind the 90%/1% principle, that
                            90 percent of all leakage can be attributed to 1 percent of the envelope area. Highlight
                            areas that have no specific detailing provided for in this 1 percent; these areas should
                            then be carefully inspected in the field. Also, make copies of all provided transitional
                            detailing to ensure in the field inspection that it was installed as required.
                         4. Highlight all waterproofing secondary or backup systems specified in the original doc-
                            uments. These systems usually can not be inspected visually in the field without com-
                            pleting destructive testing that requires the removal of some or all of the envelope
                            components to determine if these secondary systems were properly installed. Noting
                            where these systems should have been installed can assist the inspector during the field
                            inspection if they are related to the actual area of water infiltration. For example, in
                            Fig. 13.1 note the multiple secondary systems, including the membrane flashing around
                            the pipe penetration and the sealant joints under the vent cover. Neither of these sys-
                            tems would be evident in a visual inspection of the building envelope, but they play
                            important roles in waterproofing at this 1 percent of the envelope area.
   482   483   484   485   486   487   488   489   490   491   492