Page 54 - Construction Waterproofing Handbook
P. 54

2.18   CHAPTER TWO
          TABLE 2.2 Suggested Waterstop Sizing for General Conditions (Courtesy of Vinylex Corporation)

                          Maximum allowable      Minimum embedment
          Size (flange/  head of water (per Army  of flange into concrete  Minimum distance
           thickness),  Corps Engineering Manual      inches          to edge of slab/wall,
             inches       EM 1110-22101) feet                              inches
                3
            4    16              50                    1.250               2.000
                3
            9    16             100                    2.875               2.875
                3
             9    8             150                    2.875               2.875
                1
            12    2             250                    4.000               4.000














                FIGURE 2.23 Securing of PVC waterstop for first concrete placement. (Courtesy of Tamms Industries)

                                                  To secure the flange in place for both concrete place-
                                                ments, the waterstop is generally secured using wires tied
                                                to the reinforcing steel every 12 in. The wire should be tied
                                                through the first or second ribs of the waterstop flange,
                                                never going beyond the second flange as shown in Fig. 2.25.
                                                Note that in each of these details the center bulb is directly
                                                in the midpoint of the joint.  This is to ensure that the
                                                waterstop acts properly as an expansion joint during any
                                                structural movement.
                                                  The bulb must never be placed completely in one side
                                                of the placement or it will lose all its capability to act as an
                                                expansion material. Nails or any other construction debris
          FIGURE 2.24 Formwork with keyway joint sys-
          tem. Note the bulb is centered directly in midpoint  should not be allowed to puncture the waterstop bulb or
          of the joint to ensure proper functioning as an  any part of the flange near the bulb.
          expansion joint. (Courtesy of Tamms Industries)  When using waterstops at construction joints, material
                                                with bulb ends makes securing to reinforcing steel easier
                      by using wire rings that pass through the bulb but not the flange. Figure 2.26 details the
                      steps using this system for both halves of the concrete placement.
                         Placing PVC and rubber waterstops in the field usually requires some welding to joint ends
                      of rolls or making necessary changes in plane. Waterstop should never be installed by merely
                      lapping the ends together. The material must be heat-welded to fuse the ends together by using
                      manufacturer-supplied splicing irons that melt the ends that are then held together until they
                      cool, forming one continuous piece. Refer to Fig. 2.27 for a field weld application.
   49   50   51   52   53   54   55   56   57   58   59