348                                                          Appendices

         Appendix B: Calculation error of defrosting efficiency


         The calculation error of defrosting efficiency can be obtained by
                   q ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
                      2 2
                           2 2
                                2 2
             δ y ¼   a δ + a δ + a δ                                     (B.1)
                      1 1  2 2  3 3
                                                                          4
         in which δ 1 and δ 2 are the measurement errors of frost mass, m f and m v ,at10 . δ 3
                                                      2
         is the measurement error of energy consumption, at 10 . The other three parameters,
         a 1 , a 2 , and a 3 , could be calculated by,
                 ∂η d  L sf
             a 1 ¼   ¼                                                   (B.2)
                 ∂m 1  Q e
                 ∂η d  L v
             a 2 ¼   ¼                                                   (B.3)
                 ∂m 2  Q e
                 ∂η d   L sf m 1 + L v m 2
             a 3 ¼   ¼        2                                          (B.4)
                 ∂Q e       Q
                              e
         Finally, the calculation error of defrosting efficiency was calculated at  0.15%.