Page 37 - Defrosting for Air Source Heat Pump
P. 37

Previous related work: A review                                    29

           2.4.1.2 PCM-TES-based RCD

           During reverse cycle defrosting, the indoor air fan in an ASHP unit is normally
           switched off to avoid blowing cold air directly to a heated indoor space, affecting
           the thermal comfort of the occupants [90]. A defrosting operation may also occur
           at night when the ambient air temperature is lower than that during the day; sleeping
           thermal comfort may also be negatively affected [91–93]. The energy available from
           the indoor coil is basically that stored in the coil metal, but there is an insignificant
           amount of energy available from the indoor air because of a negligibly small airside
           convective heat coefficient resulting from a deenergized indoor air fan during
           defrosting. Consequently, low-pressure cut off or wet compression may take place,
           which may cause the ASHP unit to shut down and possibly damage the compressor.
           To avoid these aforementioned problems, the technologies of TES and phase change
           materials (PCM) may be applied due to the advantage of high-density energy storage
           [94]. First, DX40 was used as a thermal storage material [95] in a heat source tank for
           defrosting, and a higher defrosting efficiency was reached after using PCM-TES.
           Then, inorganic PCM such as CaCl 2  6H 2 O was used in an ASHP unit [96, 97].As
           shown, this PCM-TES-based defrosting method could help achieve improved indoor
           thermal comfort with a shorter defrosting period and a higher indoor supply air tem-
           perature during reverse cycle defrosting. The same conclusions were given in similar
           studies [98, 99]. As summarized in Table 2.7, PCM-TES-based RCD was widely stud-
           ied in 2000–2017.

           2.4.1.3 Airflow and refrigerant distribution adjustment

           Mal-distribution of refrigerant or airflow might result in uneven defrosting, thus
           degrading the defrosting performance. Aganda et al. [103] compared the predicted
           and experimental heat transfer performances for a finned tube outdoor coil, and found
           that airflow mal-distribution reduced the performances of an evaporator circuit [104].
           With refrigerant flow controlled by a TEV, the worst-performing circuit affected the
           performance of the entire outdoor coil by as much as 35%. Kim et al. [105, 106] exper-
           imentally and numerically investigated a hybrid-individual degree of superheat con-
           trol method for refrigerant flow balancing in a multicircuit evaporator: upstream vs
           downstream flow control. The results showed that the upstream refrigerant flow con-
           trol consistently outperformed the downstream refrigerant flow control, and recovered
           most of the loss in cooling capacity and COP due to nonuniform airflow distribution.
           Based on these conclusions, they utilized the model to further evaluate the effects of
           uneven air and refrigerant flow distributions and the benefits of upstream hybrid con-
           trol during defrosting for an ASHP unit [106]. Hence, adjusting airflow and/or refrig-
           erant distribution could improve defrosting performance.

           2.4.1.4 Sensible heat defrosting method
           To avoid adverse shock and “oil rush,” which were commonly seen in conventional
           RCD operations, a sensible heat-defrosting method was proposed and numerically
           investigated by Liang et al. [86], by using a self-organizing fuzzy controller in an
   32   33   34   35   36   37   38   39   40   41   42