Page 47 - Defrosting for Air Source Heat Pump
P. 47

Previous related work: A review                                    37

           outdoor coil, or the defrosting operation time duration [12]. Although the control strat-
           egy of a time-based defrosting start is widely used, a defrosting operation is not always
           terminated based on time duration. Currently, the most-used method for terminating a
           defrosting operation is based on the tube surface temperature of an outdoor coil.
           A temperature sensor is usually placed on the tube surface at the exit of the lowest
           liquid-line circuit of a vertically installed multicircuit outdoor coil [96].
           A defrosting operation will be terminated once a preset temperature is reached. It
           is obvious that when the preset temperature is higher or lower, a defrosting duration
           would be prolonged or more residual water is left, respectively. Both result in potential
           energy waste for an ASHP unit, or even degrading the indoor thermal comfort. How-
           ever, there is no standard defrosting termination temperature (DTT) or even a fixed
           range given in the application, due to the diversity of equipment and operating cli-
           mates. Different DTT settings were used and reported in 2000–2017, from 10°C
           [126] to 50°C [127], as summarized in Table 2.10. Obviously, the temperature range
           covering 40°C is too big. However, in the open literature, no relative study on
           defrosting termination temperature was reported, or was this fundamental problem
           even pointed out.
              Different strategies to start and end defrosting were studied to improve the ASHP
           system operating performance at an entire frosting-defrosting cycle. Currently, devel-
           oped time-based control strategies are widely used to start a defrosting cycle, due to
           their advantages of simplicity and reliability, although the accuracy remains




            Table 2.10 DTT settings for ASHP units (2000–2017)
                              Circuit       Capacity
            Item   DTT (°C)   number        (kW)          Year    Author

            1      10         12            55 (Cooling)  2009    Huang et al. [126]
            2      12         2             8.82 (Cooling)  2004  Ding et al. [128]
            3      15         4             55–350        2013    Wang et al. [129]
                                            (Heating)
            4      18         4             6.8 (Heating)  2010   Qu et al. [90]
            5      20         /             /             2005    Cho et al. [130]
            6      20         12            16 (Cooling)  2011    Choi et al. [88]
            7      22         12            50 (Cooling)  2004    Huang et al. [131]
            8      24         12            55 (Cooling)  2007    Huang et al. [132]
            9      24         4             6.8 (Heating)  2012   Qu et al. [96]
            10     25         2             37.5 (Heating)  2015  Dong et al. [98]
            11     26         2             4.8 (Heating)  2012   Dong et al. [110]
            12     30         4             0.88          2003    Liu et al. [23]
                                            (Compressor)
            13     33         2             2.8 (Cooling)  2012   Dong et al. [133]
            14     35         2             2.5 (Heating)  2011   Dong et al. [102]
            15     50         2             2.5 (Heating)  2011   Hu WJ [127]
   42   43   44   45   46   47   48   49   50   51   52