MAINTENANCE OF MOTORS

                                   MAINTENANCE OF MOTORS                   8.3

            APPLICATION DATA

            The first step in obtaining and maintaining adequate motor performance is the proper appli-
            cation of motors in accordance with their service conditions, which are designated as usual
            and unusual, by NEMA.


            Usual Service Conditions
            Environment

            1. Exposure to an ambient temperature in the range of 0 to 40°C (32 to 104°F) or, when
              water cooling is used, from 10 to 40°C (50 to 104°F)
            2. Exposure to an altitude which does not exceed 3300 ft
            3. Installation on a rigid mounting surface
            4. Installation in areas or supplementary enclosures which do not seriously interfere with
              the motor’s ventilation

            Operating
            1. V-belt drive in accordance with NEMA standard MG1-14.41 for ac motors or with
              NEMA Standard MG-1-14.67 for industrial dc motors
            2. Flat belt, chain, and gear drives in accordance with NEMA Standard MG-1-14.07


            Unusual Service Conditions
            1. Exposure to
              a. Combustible, explosive, abrasive, or conducting dusts.
              b. Lint or very dirty operating conditions.
              c. Chemical fumes or flammable or explosive gases.
              d. Nuclear radiation.
              e. Salty air, steam, or oil vapor.
              f. Damp or very dry locations, radiant heat, vermin infestation, or atmosphere con-
                ducive to the growth of fungi.
              g. Abnormal shock, vibration, or mechanical loading from external sources.
              h. Abnormal axial or side thrust imposed on the motor shaft.
            2. Operating where
              a. There is excessive departure from rated voltage and/or frequency.
              b. The deviation factor of the ac supply voltage exceeds 10 percent.
              c. The ac supply voltage is unbalanced by more than 1 percent.
              d. The rectifier output supplying a dc motor has current peaks unbalanced by more than
                10 percent.
              e. Low noise levels are required.
            3. Operations at speeds above the highest rated speed.
            4. Operation in a poorly ventilated room or in an inclined position.
            5. Operation where the motor is subjected to torsional impact loads, repetitive abnormal
              overloads, or reversing or electric braking.
            6. Operation of the motor at standstill with any winding continuously energized.