Page 78 - Electrical Safety of Low Voltage Systems
P. 78

The Earth    61

































                                  FIGURE 4.18 Person standing in an area at zero potential, while touching a
                                  faulted enclosure (worst-case scenario).

                                  of the area occupied by the person’s feet (i.e., at distance L from the
                                  electrode’s surface). The ground potential rises from zero to V BG =
                                  R BG I B , as shown in Fig. 4.18.
                                     A better-case scenario for safety occurs when the person is stand-
                                  ing in an area at nonzero potential at a distance l < L from the elec-
                                  trode (Fig. 4.20).
                                     The perspective touch voltage V ST is less than the earth potential
                                  V G and, in addition, the presence of the person rises the potential
                                  under his/her feet.


                                  FIGURE 4.19
                                  Equivalent fault-loop
                                  for a person standing
                                  in an area at zero
                                  potential.