Page 62 - Estimators Piping Man Hour Manual
P. 62

Section One-SHOP  FABRICATION    45

                 FLAME BEVELING PIPE FOR WELDING


                                "V" TYPE BEVELS

                                Labor For Straight Pipe Only
                                  Carbon Steel Material

                                NET MAN HOURS EACH
               Standard  Extra Hvy.
       Pipe     Pipe&     Pipe&                SCHEDULE NUMBERS
       Size   O.D.  Sizes  O.D.  Sizes
       Inches  3/8" Thick  1/8"  Thick  20  30  40  60  80  100  120  140  160
     2" Or Less  0.07      0.10              0.07  .-  0.10              0.14
     2-1/2"     0-08       0.12          --  0.08     0.12  --           0.16
     3          0.10       0.14     -        0.10     0.14           -  i  0.19
     4          0.14       0.19          ..  0.14  -  0.19  --  0.26     0.28
     5          0.17       0.24     -       0.17  -   0.24  --  0,30     0,34
     6          0.23       0.30     -    --  0.23  -  0.30      0.39     0.43
     8          0.32       0.44    0.32  0.32  0.32  0.40  0.44  0.52  0.59  0.65
     10         0.44       0.63    0.44  0.44  0.44  0.63  0.68  0.75  0.83
     12         0.48       0.75    0.48  0.48  0.59  0.89  0.94  1.03  --  ..
     14O.D,     0.67       0.89    0.67  0.67  0.79  0.98  1.14  -  ..  j

     160.D.     0.75       1.10    0.75  0.75  1.10  1.22  1.35  -
     18O.D.     0.94       1.34    0.94  1.10  1.34  1.50  --  --  „    j  .,
     20 O.D.    1.14       1.50    1.14  1.54  1.65  1.82  -  --
     240.D.     1.73       2.20    1.73  2.32  2.44
                                                                        _L
     For mitre bevels add 50% to the above man hours.
     Above man hours are for flame "V" beveling only and do not include cutting or internal machining. See respective
     man hour tables for these charges.
     For beveling on the ends of bends or shop trimmed fittings, add 50% to the  above man  hours.
     The above man  hours are for wall thicknesses of 7/8" or less. For wall thicknesses  greater than 7/8" refer to man
     hours on following  pages.
   57   58   59   60   61   62   63   64   65   66   67