Page 484 - Forensic Structural Engineering Handbook
P. 484

MASONRY STRUCTURES                   13.29

             Architectural Failures
             Water Permeance.  Water permeance is the leading cause of masonry’s failure to perform
             as intended. Water damage may include dimensional change, corrosion, decay, florescence,
             freeze-thaw spalling or splitting, increased heat transmission, condensation, deterioration
             of interior finishes and building contents, and tenant inconvenience.
               Four inches of unit masonry, no matter how built, by whom, or of what material, never
             stopped a wind-driven rain. Rain does not permeate through masonry units or mortar in sig-
             nificant quantities. It enters through cracks between units and mortar. Figure 13.2 shows
             definitions of mortar joint locations. Figure 13.25 shows recommended mortar joint con-
             figurations. Unfilled mortar joints and raked mortar joints increase leakage. Grimm
                                                       29
             describes problems associated with unfilled mortar joints and the importance of mortar
                    32
             materials. Drainage-type walls collect penetrating water and redirect it to the exterior by
             flashing through weep holes. Weep holes should be provided 24 to 32 in (600 to 813 mm)
             on center immediately above flashing.
               It is virtually impossible for a mason to keep a 1-in (25-mm) airspace clean of mortar
             droppings, because a trowel cannot be maneuvered in such a narrow space, especially if the
             mason cannot see the space, as depicted in Fig. 13.26. However, mortar droppings in a
             2-in (50-mm) or wider cavity, as shown in Fig. 13.27, can be avoided by beveling rather
             than furrowing mortar bed joints.
               Flashing is typically improperly detailed, specified, and installed. There are at least 106
             types of through-wall flashing with costs ranging over one magnitude. Manufacturers guar-
             antee a life expectancy of 5 years for a product that is supposed to protect a wall for 100 years.
             Figure 13.28 illustrates flashing terminology. Flashing end dams, shown in Fig. 13.29 and
             corner flashing shown in Fig. 13.30, are particularly important. Through-wall flashing should
             extend beyond the face of the wall and turn down to form a drip, as shown in Fig. 13.31.
             Otherwise, water enters the wall below the flashing. Figure 13.32 shows the consequences of
             not providing a proper sealant joint and lipped fascia. Flashing should not extend through
             movement joints and should be provided at the following locations with joints lapped 6 in
             (150 mm) and sealed: heads of wall openings, wall spandrels and bases, intersections of
             walls with floor and roofs, under copings and sills, and above lintels and shelf angles.










                    Concave              “V”             Flush*




                              Struck*           Beaded*            Raked*

                                                  *Not recommended for exterior use
                                                  where the driving rain index > one.
                  Weathered*          Extruded*

             FIGURE 13.25  Recommended mortar joint configurations.
   479   480   481   482   483   484   485   486   487   488   489