Page 213 - HVAC Pump Handbook
P. 213

Rishel_CH08.qxd  21/4/06  6:16 PM  Page 210




                                       The Use of Water in HVAC Systems

                    210   The HVAC World

                    higher water temperatures to avoid condensing. Noncondensing boil-
                    ers cannot operate with water at temperatures below 140°F. The
                    development of the condensing boiler has enabled the designer to
                    select great differential temperatures between the supply and return
                    temperatures. This has reduced appreciably the water flow and,
                    therefore, the pump flow and horsepower.
                      Likewise, on chilled water systems, it is recognized that chillers
                    operate at lower kilowatt per ton rates with higher chilled water tem-
                    peratures. In recognition of these facts, HVAC water systems should
                    be designed for lower hot water temperatures and higher chilled
                    water temperatures. Reset of system water temperature at boilers or
                    chillers should be used rather than zone reset in most cases. Zone
                    reset should use efficient pumping such as distributed pumping,
                    which will be described in Chaps. 15 and 20 on chilled and hot water
                    distribution systems.
                      Condenser water systems are realizing greater efficiencies through
                    the use of variable-speed pumps. The types of controls that are avail-
                    able today for removing heat from the chillers have allowed the use of
                    these variable-speed condenser pumps. The consumption of energy for
                    boiler feedwater is relatively less than that for the other major HVAC
                    water systems.

                    8.1.1 Determination of useful energy
                    The advent of digital electronics, as discussed in Chap. 1, provides the
                    means to determine rapidly the efficient use of pumping energy for all
                    HVAC water systems. It remains for us to develop what is efficient
                    use and what is not. Following are some guidelines that will help us
                    in this determination of the value of various practices that consume
                    pumping energy.
                      Useful consumption of pumping energy
                    1. Pipe friction required to transport water
                    2. Friction in fittings to connect the pipe
                    3. Friction in heating and cooling coils
                    4. Properly sized pumps and motors
                    5. Properly selected variable-speed drives
                    6. Friction in properly evaluated chillers and boilers

                      Inefficient use of energy
                    1. Temperature-control valves
                    2. Balance valves, manual or automatic




                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   208   209   210   211   212   213   214   215   216   217   218