                                       The Use of Water in HVAC Systems

                    212   The HVAC World

                    central plant generation of hot and chilled water is not included in
                    the distribution system COP. Plant COP is determined in the chap-
                    ters on chillers and boilers.

                    All hot water radiation system. This system consists of just radiation of
                    various types without fans or blowers and is shown in Fig. 8.1. The
                    equation for COP is:
                                                                      −
                                                  −  T 1)  0.147 Q s  (T 2 T 1)
                                      500   Q s   (T 2
                               COP                                               (8.2)
                                          3413   W p            W p
                    where Q  hot water system flow, gal/min
                            s
                          T  system supply water temperature, °F
                            2
                          T  system return water temperature, °F
                            1
                          W  kilowatt input to pump motors
                            p
                    Air-water system. This system is a combination of radiation and air-
                    handling units and is typical of a large percentage of hot water and
                    chilled water systems. They are shown in Fig. 8.2 and the equation for
                    the COP is developed in Eq. 8.3.
                                                             −
                                              0.147   Q s   (T 2  T 1)
                                       COP
                                                        +
                                                     W p  W f                    (8.3)
                    where W  kilowatt input to fan motors
                            f
                     (T − T )  difference between the supply and return water
                       2   1
                               temperatures




                      Pumps     W p   T 1     Q s


                           From boilers
                                                      Radiators








                                      T 2
                         To boilers
                    Figure 8.1  All-radiation system.