Page 317 - HVAC Pump Handbook
P. 317

Rishel_CH10.qxd  21/4/06  6:20 PM  Page 314




                                   Basics of Pump Application for HVAC Systems

                    314   The HVAC World

                      Most pump controllers are now based on digital electronics and are
                    of the proportional-integral-derivative or digital type, which sense a
                    signal, compute the error, and output the speed signal to the variable-
                    speed drive. Since the speed of the pump is held at a discrete point by
                    such a controller until it is updated, there can be continuous speed
                    fluctuation when rapid control response is not provided. Standard
                    commercial PID computer chips are available with a rate of response
                    as fast as 10 to 500 ms. Rate of response should not be a problem on
                    variable-speed HVAC pumps due to the digital technology that is now
                    available for the control of such pumps. Any variable-speed pump that
                    has continuous speed change is not being controlled properly. It may
                    have too slow a speed response from the transmitters that are con-
                    trolling the pump speed.
                      Although standard commercial computer chips are designed for
                    proportional-integral-derivative control, most HVAC applications do
                    not require any derivative value inserted in the actual control algo-
                    rithm. Also, proportional-integral controllers of the analog type are
                    seldom used in this industry.


                    10.11.5 Sensors for pump speed control
                    The preceding description of basic variable-speed control listed the
                    types of sensors used for pump operation. Some HVAC systems
                    require more than one sensor to maintain the proper speed of the
                    pumps. This is due to shifting heating or cooling loads on the water
                    system. The standard signal-selection technique is utilized to accom-
                    modate more than one transmitter (Fig. 10.20b). The controller selects
                    the transmitter at which the signal has deviated the farthest from its
                    set point. Following is information on the selection and location of
                    sensors or transmitters.
                      The location of the sensors is important to ensure that the pumps
                    can be operated at the lowest possible speed from minimum to maxi-
                    mum system load. See Chap. 10 for proper sensor location for specific
                    types of water systems.
                      When pressure or differential pressure is used to control pumps,
                    these transmitters must be located so that the distribution friction
                    pressure loss of the system is eliminated from the signal. For exam-
                    ple, assume that a distribution system for a hot or chilled water sys-
                    tem consists of differential pressure with direct return piping and has
                    a 20-ft loss across the largest coil, its control valve, and piping. Also
                    assume that the distribution friction loss out to and back from the
                    farthest coil is 80 ft. The total pump head is therefore 100 ft. If the
                    pressure transmitter is located at the pump, it must be set at 100 ft to





                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   312   313   314   315   316   317   318   319   320   321   322