                                   Basics of Pump Application for HVAC Systems

                                            Basics of Pump Application for HVAC Systems  319






















































                    Figure 10.23 Use of control-valve position for differential pressure reset.

                      All valves 70 percent open:  16 ft
                      All valves 60 percent open:  14 ft
                      All valves 50 percent open:  12 ft
                      3. Return water temperature control.  Fortunately, this method of
                    control is not seen very often. It absolutely will not work! Return




                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)