Page 324 - HVAC Pump Handbook
P. 324

Rishel_CH10.qxd  21/4/06  6:20 PM  Page 321




                                   Basics of Pump Application for HVAC Systems

                                            Basics of Pump Application for HVAC Systems  321

                    at the remote differential pressure transmitter and at the pumping
                    system. This procedure allows the use of ordinary telephone cables for
                    transmission of the control signals.
                      Care should be taken to avoid routing the control signals through
                    building management systems that reduce the rate of response from
                    the transmitter; the signal and data load on these central manage-
                    ment systems may be such that the transmitter signal for pump
                    speed control cannot be processed faster than 2 to 4 seconds. This is
                    too slow for accurate pump speed control. This must not occur rou-
                    tinely or when the central management system is responding to emer-
                    gency conditions such as fire or building power failure.


                    10.12 Effects of Water Systems
                    on Pump Performance
                    The pump is the heart of every water system; when it fails, the sys-
                    tem fails. Unfortunately, many times pump failure is due to the water
                    system’s effects on the pump’s performance and physical condition.
                    The problems with cavitation and entrained air on pump performance
                    and damage have already been discussed in Chap. 6.
                      Other deleterious effects on pumps are control systems that force
                    pumps to run in the high-thrust areas, namely, at very low or high
                    flow rates. The pump wears rapidly, and it is not the pump’s fault.
                      One of the most disastrous practices in pump application is the
                    installation of a relief valve on a pump discharge that returns the
                    water to the pump suction, as shown in Fig. 10.24a. It should be
                    remembered that the thermal equivalent of a brake horsepower is
                    2544 Btu/h. All the energy destroyed by the relief valve is returned to
                    the pump suction. If the system is operating at low loads, where the
                    flow through the pump is low, it is very apparent that heat will build
                    until the pump can become very hot. Also, hot water will surge
                    through the system when the flow does increase.
                      Relief valves should be avoided wherever possible on chilled water
                    systems because every brake horsepower destroyed by the relief valve
                    adds one-fifth of a ton load on the chillers. If there is no other way to
                    control the water through the system than by a relief valve, it should
                    be connected as shown in Fig. 10.24b. The heat is returned to the
                    chiller, and the pump continues to receive and deliver chilled water.
                      Heating and cooling coils that are dirty on the air or water side or
                    are operating with laminar flow increase the system flow beyond the
                    design flow rates. Often pumps are blamed for their inability to provide
                    these greater flows; good system control is the answer for many system
                    problems that cause unnecessary pump wear and maintenance.





                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   319   320   321   322   323   324   325   326   327   328   329