Page 323 - HVAC Pump Handbook
P. 323

Rishel_CH10.qxd  21/4/06  6:20 PM  Page 320




                                   Basics of Pump Application for HVAC Systems

                    320   The HVAC World

                    water temperature has no relationship to system load on variable-
                    volume systems; it should be maintained as closely as possible to a
                    constant value. For example, a chilled water system operating with
                    44°F supply temperature and 56°F return temperature should hold
                    these temperatures whether the load is heavy or light on the system. There-
                    fore, return temperature cannot possibly be used as a control parameter for
                    variable-speed pumping. Often there has been confusion of variable
                    return water temperature that results from the use of three-way
                    valves; these systems were, of course, constant-volume systems and
                    not used with variable-speed pumps for most applications.

                    10.11.6 Communication from
                    remote transmitters
                    The method of communication with remote transmitters is particu-
                    larly important to ensure that a noninterrupted signal is received at
                    the pump controller at the rate of response specified by the pump con-
                    trol manufacturer. The route that the signal takes is of importance to
                    the water system designer.
                      Most signals from remote transmitters are direct current and 4 to
                    20 mA in strength. These signals must be protected from electromag-
                    netic and radiofrequency interference. Therefore, the interconnecting
                    cabling must be shielded and grounded at the pump controller end.
                    Table 10.11 provides typical distances between the transmitter and
                    the pump controller that can be used with various sizes of wire.
                      These cables can be installed in conduit or cable trays that carry
                    other instrument, data, or telephone signals. They must be shielded
                    for electromagnetic and radio frequency interference, and the shield
                    must be grounded at the end of the cable near the pumping system
                    controller.
                      On some large installations, the cable installation for pump control
                    can become expensive; an alternate procedure is to install modems


                    TABLE 10.11 Maximum Linear
                    Distances for Transmitters from Pump
                    Controllers
                     Wire size, AWG   Linear distance, ft
                          16              20,000
                          18              11,000
                          20                8000
                          22                5000
                          24                3500
                          26                2000





                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   318   319   320   321   322   323   324   325   326   327   328