Page 34 - HVAC Pump Handbook
P. 34

Rishel_CH02.qxd  20/4/06  5:13 PM  Page 31




                                     Physical Data for HVAC System Design

                                                  Physical Data for HVAC System Design  31

                    TABLE 2.8 Standard 60-Hz Voltages

                                             Motor nameplate voltage
                      Nominal distribution
                      system voltage      Below 125 hp   125 hp and up
                      Polyphase
                        208                   200            —
                        240                   230            —
                        480                   460            460
                        600                   575            575
                       2400                  2300           2300
                       4160                  4000           4000
                      Single-phase
                        120                   115            —
                        208                   200            —
                        240                   230            —

                      SOURCE: AC Motor Selection and Application Guide, Bulletin GET
                    6812B, General Electric Company, Fort Wayne, Ind., 1993, p. 2; used
                    with permission.



                    TABLE 2.9 Standard 50-Hz Voltages
                       Nominal distribution   Motor nameplate voltage
                          system voltage    Below 125 hp  125 hp and up
                     Polyphase (see note) 200   200
                                                220          —
                                                380          380
                                                415          415
                                                440          440
                                                550          550
                                               3000         3000
                      Single-phase (see note)   110          —
                                                200          —
                                                220          —
                      NOTE: Distribution system voltages vary from country to country;
                    therefore, motor nameplate voltage should be selected for the country
                    in which the motor will be operated.
                      SOURCE: AC Motor Selection and Application Guide, Bulletin GET
                    6812B, General Electric Company, Fort Wayne, Ind., 1999, p. 2; used
                    with permission.



                    have standardized on 50 Hz; there also may be rural areas of the
                    United States still operating on 50-Hz power. Tables 2.8 and 2.9 pro-
                    vide nominal power distribution voltages and standard nameplate
                    voltages for motors operating at both 60 and 50 Hz. Electric power
                    utilities are allowed a variation of  5 percent from the distribution
                    system voltages listed in these tables.