Page 343 - HVAC Pump Handbook
P. 343

Rishel_CH11.qxd  20/4/06  6:37 PM  Page 340




                                         Open Cooling Tower Pumps

                    340   Pumps for Open HVAC Cooling Systems

                    TABLE 11.2 Pumping System Analysis for Chillers in Fig. 11.6b

                       Condenser water   No. of pumps                      Wire-to-wire
                       flow, gal/min    running    System bhp    Input kW   efficiency, %
                          1500            1           20.0         17.8       56.6*
                          3000            1           36.6         31.0       68.6*
                          4500            1           66.1         54.1       63.5
                          4500            2           60.8         52.1       66.0*
                          6000            2           86.3         72.0       69.8*
                          7500            2          121.3         99.4       70.0*
                          9000            2          167.8        135.7       68.7
                          7500            3          122.9        102.5       67.9
                          9000            3          161.3        132.7       70.3*
                      *Optimal number of pumps.


                    number of chillers (Fig. 11.7b), the variable-speed pumps also can be
                    controlled by the pressure drop across the condensers. As a chiller is
                    started or stopped, the control valve on the chiller condenser water
                    circuit opens and closes. The optimal number and size of pumps
                    appear to be three 50 percent system capacity pumps on most of the
                    multiple-chiller applications. Table 11.2 is a tabulated analysis of the
                    pumps for the chillers in Fig. 11.7b.
                      This wire-to-water efficiency analysis indicates the number of
                    pumps that should be run with various chillers in operation. Even
                    though two pumps are required to handle the maximum load of 9000
                    gal/min, this evaluation indicates that it is more efficient to operate
                    all three pumps at full load.

                    11.6.1 Operating absorption and
                    centrifugal chillers together
                    A problem that the variable-speed pump is solving is the operation of
                    an absorption and an electric chiller from the same cooling tower
                    installation. In the past, this was unacceptable because of the differ-
                    ence in condenser supply water temperatures. The absorption
                    machine required fairly constant supply water temperature, while the
                    electric chiller preferred colder condenser water that improved its
                    performance. With variable-speed condenser pumps, the inlet water
                    temperature to the condenser no longer need be a constant. With vari-
                    able flow through the condenser, the control procedure now is to
                    maintain the heat balance in the condenser like any other heat
                    exchanger. The variable-speed pump for the electric machine is con-
                    trolled by the lift pressure of the chiller, while the absorption machine
                    is controlled by leaving water temperature and minimum flow. If the
                    cooling tower water drops as low as 60°F, it may be necessary to reset




                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   338   339   340   341   342   343   344   345   346   347   348