Page 50 - HVAC Pump Handbook
P. 50

Rishel_CH03.qxd  20/4/06  5:35 PM  Page 47





                                           Piping System Friction
                                                               Piping System Friction  47

                    TABLE 3.5 Flow of Water in Steel Pipe  (Continued )
                                        42-in inside
                                         diameter
                                               V  2        h, ft per

                     Flow, gal/min  V, ft/s    2 g, ft   100 ft of pipe
                        001000       0.232    0.00083      0.00047
                        001500       0.347    0.00187      0.00098
                        002000       0.463    0.00333      0.00164
                        002500       0.579    0.00521      0.00246
                        003000       0.695    0.00750      0.00343
                        003500       0.811    0.0102       0.00454
                        004000       0.926    0.0133       0.00580
                        004500       1.042    0.0169       0.00720
                        005000       1.16     0.0208       0.00874
                        006000       1.39     0.0300       0.0122
                        007000       1.62     0.0408       0.0162
                        008000       1.85     0.0533       0.0208
                        009000       2.08     0.0675       0.0258
                        010000       2.32     0.0833       0.0314
                        012000       2.78     0.120        0.0441
                        014000       3.24     0.163        0.0591
                        016000       3.71     0.213        0.0758
                        018000       4.17     0.270        0.0944
                        020000       4.63     0.333        0.115
                        025000       5.79     0.521        0.176
                        030000       6.95     0.750        0.250
                        035000       8.11     1.02         0.334
                        040000       9.26     1.33         0.433
                        045000      10.420    1.69         0.545
                        050000      11.6      2.08         0.668
                        060000      13.9      3.00         0.946
                        070000      16.2      4.08         1.27
                        080000      18.5      5.33         1.66
                        090000      20.8      6.75         2.08
                        100000      23.2      8.33         2.57
                                                 2
                      NOTE: V   velocity, feet per second; V /2g   velocity head, feet;
                    Hf   friction loss, feet per 100 feet of pipe. No aging factor, manufac-
                    turer’s tolerance, or any factor of safety has been included in the
                    friction losses Hf.
                      SOURCE: Data in this table have been derived from the
                    Engineering Data Book, 2d ed., Hydraulic Institute, Parsippany,
                    N.J., 1990.












                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.