                                           Piping System Friction
                    74   The Basic Tools














































                    Figure 3.11 Friction loss in schedule 80 PVC and CPVC, IPS-OD. (Reprinted by permis-
                    sion from “Engineering & Specifications Manual,” IPEX, Inc., 2000.)



                    representation of Bernoulli’s theorem. The vertical dimension of these
                    diagrams is to scale and is shown normally in feet of head (see Eq. 4.1
                    for computing feet of head from known pressures and temperatures).
                    The horizontal dimension is not to scale and is used to separate the
                    specific changes in static and friction losses in various parts of the
                    system.
                      Pump head is usually shown vertically upward, while friction losses
                    can be shown vertically downward or diagonally. Computer programs
                    are now being evaluated to facilitate the development of diagrams
                    similar to those shown here.