Page 162 - Handbook of Electrical Engineering
P. 162

SWITCHGEAR AND MOTOR CONTROL CENTRES        145

                                  Table 7.1.  Busbar normal current ratings in amps

                                 HV MCCs and SWBDs     LV MCCs and SWBDs
                                          400
                                          630                  800
                                          800                 1600
                                         1200                 2400
                                         1600                 3000
                                         2000                 3150
                                         2400                 3500
                                         3000                 4000
                                         3150

           vertical busbars in low voltage motor control centres. Often in oil industry motor control centres there
           is a mixture of motor controllers and static load feeder units. Motors seldom need a 4-wire supply
           but static loads are often unbalanced and require the fourth or neutral wire. The motor and static load
           units need not necessarily be segregated into different complete vertical assemblies, although this is
           good engineering practice, and so it is advisable to specify a fourth vertical busbar in each vertical
           assembly. When a 4-wire system is required the incoming and busbar section circuit breakers may
           be 3-pole with a linked neutral or be 4-pole. If the SWBD or MCC feeds equipment located in a
           hazardous area then the 4-pole circuit breakers should be used, as recommended in the international
           standards, see Chapter 10.
                 For balanced loads and for voltages above 1000 V a 3-wire source is used and hence only
           three busbars are needed. Unbalanced loads are seldom encountered at high voltages. Typical busbar
           normal current ratings used in the oil industry are shown in Table 7.1.

                 The maximum value of 4000 A for low voltage busbars roughly corresponds to the secondary
           current of a fully loaded 2500 kVA transformer. 2500 kVA is often chosen as the limit for transformers
           that feed motor control centres because the fault current that they allow through is typically near to the
           limit that the manufacturers can normally supply, e.g. 80 kA symmetrical rms current. A 2500 kVA
           transformer with a 6% leakage impedance and a 400 V secondary winding will pass approximately
           60 kA of fault current. If the MCC feeds mostly motors then they will collectively contribute some
           fault current in addition to that from the transformer, see IEC60363 clause 4 and IEC60909 clause
           13. In the above simple example some of the margin between 60 kA and 80 kA will be taken up by
           the sub-transient contributions from the motors. It can be noted at this point that if the transformer is
           subsequently increased in rating by the addition of forced air fans, then the fault current passed by
           the transformer will be unchanged. It is advisable to specify the rating of the transformer in its forced
           air-cooled mode of operation, if such cooling is considered likely to be needed in the future. This
           would ensure that the incoming circuit breakers and busbar normal rated currents would be correctly
           matched to the transformers.
                 High voltage switchboards are available with busbar ratings up to 5000 A. Consider for
           example an 11 kV switchboard that is fed by four 25 MVA generators, two connected to the left-hand
           side busbar section and two on the right-hand side section. The total rated current from a pair of
           generators is 2624 A, which is the maximum current that can flow across the busbar section circuit
           breaker. Hence the busbars can be adequately rated at 3000 A or 3150 A for this plant.
                 Busbars are mounted on insulated bushes that are strong enough to withstand the peak short-
           circuit currents and forces. The busbars may be air insulated or enclosed in an insulating sleeve.
   157   158   159   160   161   162   163   164   165   166   167