Page 163 - Handbook of Electrical Engineering
P. 163

146    HANDBOOK OF ELECTRICAL ENGINEERING

              The sleeve is used where the atmosphere may be damp or corrosive. Neutral busbars are usu-
              ally rated at half the phase busbar current ratings. If the neutral is likely to carry harmonic cur-
              rents then it is good practice to use a fully rated neutral busbar i.e. the same as the individual
              phase busbars.


              7.2.2 Earthing Busbars

              The earthing (grounding) busbar is separate from the neutral busbar, and is used to earth all conductors
              that need to be earthed as well as the metallic frame and casing of the switchboard or motor control
              centre. The earthing busbar is made of high-grade copper and is usually located at the front or rear
              of the enclosure at ground level.


              7.2.3 Incoming and Busbar Section Switching Device

              7.2.3.1 Low voltage systems up to 600 V

              The incoming and busbar section switching devices are usually air-break circuit breakers, which can
              be fixed or withdrawable from the main frame or enclosure. They can be 3 or 4-pole depending upon
              whether a 3 or 4-wire supply is required. Some low power switchboards may use load-break switches
              for these functions.


              7.2.3.2 High voltage systems up to 15 kV

              Several types of circuit breakers are available for high voltage operation. The main types are:-
              • Air-break.
              • Sulphur hexafloride gas.
              • Vacuum.

                    The use of oil in switchgear has become unnecessary and discontinued. The choice of circuit
              breaker type for a particular power system depends upon several main factors:-
              • Ambient and environmental conditions, derating may be required for high ambient temperatures.
              • Rated normal rms current.
              • Fault peak making current with the appropriate DC offset.
              • Fault rms breaking current with the appropriate DC offset if it is still present.
              • Fault withstand duty.
              • Cost and economics.
              • Variety of choice in the market so that a technical and economic comparison can be made.
              • Physical size and suitability for the intended location.
              • Manufacturing time and delivery time.
              • Obsolescence and the availability of spare parts.
              • Post purchase follow up services.