Page 276 - Handbook of Electrical Engineering
P. 276

HAZARDOUS AREA CLASSIFICATION      261

                                   Table 10.6. Ingress protection against liquids

                   Forth digit             Brief description of the protection provided
                                                against liquids (typically water)
                       0        No mechanical protection
                       1        Water droplets falling vertically, i.e. condensation droplets, not heavy
                                  rainfall
                       2        As for 1, except that the enclosure can be inclined in angle up to 15 ◦
                                  from its normal position
                       3        Rain water or sprayed water.
                                                            ◦
                                Falling vertically or at angle up to 60 from the vertical (horizontal
                                  spray is excluded e.g. man with a hose pipe)
                       4        Water being splashed from any direction e.g. rain water hitting the
                                  ground, but not under pressure
                       5        Water applied by jets from any direction e.g. hose pipe with a nozzle
                       6        Conditions on the deck of a ship (or offshore platform), during stormy
                                  seas and high waves; this implies good water tightness at atmospheric
                                  pressure
                       7        Submersed in water at a given depth for a given time e.g. 1 m depth for
                                  30 minutes; this prescribes a hydrostatic pressure greater than
                                  atmospheric pressure
                       8        Submersed in water at a given depth for an indefinite time; this implies
                                  that almost complete protection is provided

           The protection against liquids is summarised in Table 10.6:
                 It can be seen in practice that the design of a jointed surface or an enclosure grill to protect
           against particles will, by its physical construction, satisfy to some extent the requirements for ingress
           of liquid. Table 10.7 shows an approximate relationship between the two requirements, and shows
           those codes which are generally available from manufacturers.
                 When hazardous area equipment is being specified, it will need to be given a minimum degree
           of ingress protection. The degree will depend upon whether the equipment is to be installed outdoors
           and exposed to the extremes of the weather, or indoors and exposed (or not) to dust or liquid ingress.
           The degree may also depend upon whether the equipment is located at ground level or, for example,
           attached to a ceiling in a plant room. If the location is outdoors, then the IP code will typically
           vary between IP54 and IP66. For indoor equipment in a hazardous area not exposed to particles or
           water, the minimum IP code would be typically IP44. The installation designer should consult the
           manufacturers of particular types of equipment e.g. motors, luminaries, in order to determine what
           minimum IP is normally available. It is often easy to overspecify equipment by being too cautious or
           conservative, and this results in severely restricting the manufacturers that are available in the market
           place or they will decline to offer equipment. This causes delay in a project and necessitates revising
           a specification and repeating the enquiry process.


           10.6.2 American Practice
           A similar approach to the IP code is used in the USA and is described in the ANSI/UL and ANSI/ISA
           standards but a ‘Type Number’ is used instead of the two or four digit code (n, m, a, s). The
           basic principles are very similar. Reference 2 Article 500-4 summarises the subject and quotes the
           appropriate codes and standards.