Page 295 - Handbook of Electrical Engineering
P. 295
FAULT CALCULATIONS AND STABILITY STUDIES 281
The contribution from the lower voltage motors is found as follows.
The average ratio of starting current to rated current (I s /I n ) for the lower voltage motors may be
assumedtobe,
I s
= 6.5 pu for lower voltage motors
I n
Their sub-transient impedance Z is
lm
1.0
Z lm = = 0.153 pu(at S lm )
6.5
Typical lower voltage motors have a starting power factor of between 0.25 and 0.35 lagging,
hence assume 0.35.
The sub-transient impedance Z of the motors becomes,
lm
Z lm = 0.054 + j0.143 pu
The equivalent impedance Z td of the distribution transformers can be found by the method in
sub-section 11.5.2.5 or taken as,
Z td = 0.0 + j0.055 pu(at S td )
Again assume that the air-gap emf E is 1.0 pu.
lm
The contribution I from the lower voltage motors is,
lm
E lm
I
lm =
Z
lm Z td
+ S base
S lm 2K td (S lm + S ls )
1.0S lm
(11.3)
j0.06
=
0.054 + j0.143 + S base
K td2
Where
S ls
K td2 = 2K td 1.0 +
S lm
The total sub-transient symmetrical rms fault current I is,
frms
I = I + I + I (11.4)
frms g hm lm
11.6.1 Calculate the Sub-Transient Peak Fault Current Contributions
Many power system networks can be reduced to a simple series-connected circuit containing a resis-
tance R and an inductance L, for the purpose of calculating the transient fault current. Furthermore a