Page 301 - Handbook of Electrical Engineering
P. 301

FAULT CALCULATIONS AND STABILITY STUDIES     287


































           Figure 11.10 Short-circuit current waveform of a series-connected R-L circuit that is fed by a sinusoidal
           voltage. The switching angle θ is −90 degrees, which represents the worst case. The responses are for eight
           values of the circuit X-to-R ratio.

           is small i.e. X-to-R ratios greater than about 5.0. Hence substituting for ωt = π gives the doubling
           factor (DF) as,
                                                    −Rπ
                                                 ∼
                                             DF = e  x  + 1.0
                 For intermediate X-to-R ratios i.e. 0.1 to 5.0, the equality in (11.7) must be satisfied, which
           is best achieved by iteration for a solution in the vacinity of ωt = 3π/4, e.g. by Newton’s method,
           see Reference 4.
           Figure 11.10 shows ‘worst-case’ responses of i for different values of the ratio X to R.


           11.7 APPLICATION OF THE DOUBLING FACTOR TO FAULT CURRENT
                 I      FOUND IN 11.6
                  frms

           Now returning to the rms equations for I , I      and I      in sub-section 11.6 it can be seen that each of
                                             g  hm     lm
           these currents can have different X-to-R ratios and will therefore decay at different rates. The peak
           fault current is,
                                         √

                                   I      =  2(DF g I + DF hm I      + DF lm I )

                                    fpk          g         hm       lm
                 Where the doubling factors DF g , DF hm and DF lm are evaluated from the X-to-R ratios of
           each component using equation (11.5) or their nearest ratio given in Table 11.3 as I 1 (pu) or in
           Table H.1b.
   296   297   298   299   300   301   302   303   304   305   306