Page 160 - Hybrid-Renewable Energy Systems in Microgrids
P. 160

144                                 Hybrid-Renewable Energy Systems in Microgrids


























         Figure 7.18  Short-circuit current leaving Bus 3 under unbalanced faults in the middle
         of line 3-4 with prefault condition (2) (A) Balanced current control, A-B fault. (B) Balanced
         current control, A-g fault.
























         Figure 7.19  Short-circuit current leaving Bus 3 under unbalanced faults in the middle
         of line 3-4 with prefault condition (3) (A) Balanced current control, A-B fault. (B) Balanced
         current control, A-g fault.

         which is similar to a traditional power system. However, this kind of logic does not apply
         for a microgrid operating under islanded mode when there is no support from the utility
         grid. In contrast, the short-circuit contribution from converters is restricted in each phase
         considering their limited overload capabilities of semiconductors. This results in a much
         lower short circuit current level in an islanded mode microgrid.