Page 157 - Hybrid-Renewable Energy Systems in Microgrids
P. 157

Study of control strategies of power electronics during faults in microgrids    141




























           Figure 7.16  Short-circuit current leaving Bus 3 (A) A-B fault. (B) A-g fault.

           (1) P VSI1  = 40 kW, P VSI3  = 10 kW, all loads equal to 8.07 kW; (2) P VSI1  = 10 kW,
           P VSI3  = 60 kW, all loads equal to 8.07 kW; (3) P VSI1  = 40 kW, P VSI3  = 10 kW, all loads
           equal to 8.07 kW with load 1, 2, and 3 switched off; For all scenarios, VSI 2 will pro-
           vide the remaining active power including line loses to keep the generation and load
           balance. With different control strategies of VSI 1, Fig. 7.17 presents some examples
           of the short circuit current leaving Bus 3 subject to unbalanced faults in the middle of
           the line 3-4 for prefault condition (1). With all control strategies fixed at balanced cur-
           rent control strategy, Figs. 7.18 and 7.19 present the short-circuit current for prefault
           condition (2) and (3), respectively. In contrast, the short-circuit current leaving Bus 4
           toward fault location is also examined in the study. However, the changes of control
           strategies in VSI 3 do not have so much impact on the short circuit current in this side.
           As VSI 3 is electrically far away from the fault location and it tends to deliver active
           power to the loads nearby, the short circuit current on this side is mainly provided by
           VSI 2, whose control strategy is fixed at balanced current control.


           5.4  Discussion on microgrid protection
           The short-circuit currents for the same fault type and location differ from each other sig-
           nificantly under grid-connected and islanded operation of the microgrid. By comparing
           Figs. 7.17–7.19 to Fig. 7.16, the short-circuit current in islanded operation is much lower
           than that of grid-connected operation, which indicates that a unique setting of an over-
           current relay will not function well for a mircogrid application. When the microgrid is
           grid-connected, it is relatively easier to identify the faulty phases based on current ampli-
           tude as most of the short-circuit current is contributed by the utility grid. For example,
           the currents in phase A and B are much higher than that of phase C under an A-B fault,
   152   153   154   155   156   157   158   159   160   161   162