Page 764 - Industrial Power Engineering and Applications Handbook
P. 764

Grounding practices 22/721
         Tolerable touch voltage                        n, = no. of conductors lengthwise
                                                         b = width of the grid in m
                                 0.116                  nb = no. of conductors widthwise
                                  Ji                     a = length of the grid in m and
          E,,50, 5 (1.5 c,  p,  + 1000) x  ~
         for a 50 kg body                       (22.7)   n  = no  of grounding rods
                                                         a = depth of grounding rods in m
                                 0.157
          Et(,,), 5 (I .5 c,  p, + 1000) x __           (ii)  For grid depths > 250 mm
                                  zit
         for a 70 kg body                       (22.8)

         Design parameters
                                                        where A  = a . b
          I,  = lg . Dt                         (22.9)
          I,  = maximum ground fault current
          Zg  = symmetrical ground fault current        Measuring average resistivity of soil
          D, = decrement factor
                                                        p=2mR,                               (22.15)
         Body resistance
             f??t$h = 6 . c, . p, + Rh                  Minimum size of grid conductors
                 = 6. C, . p, + 1000           (22.10)                        1;
                                                               A=                            (22 161
             f??fsh  = total  touch resistance through the body
              Rh = body  resistance
         and.
                                                               A  = cross-sectional  area  of  ground conductor
             Rzf,,\ = 1.5 x c\ ' p& + Rh                           in mm2
                                                              1;  = ground fault current in kA  (r.m.s.)
                 = 1.5 x c, ' p\ + 1000        (22.11)
                                                                 = it  may  be  substituted  with  I,  (equation
             R2fp5 = total  step resistance through the body       (22.9))
              C, = reduction factor for derating the nominal value   Tcap = thermal capacity factor in Jlcm'/"C
                  of surface layer resistivity,  corresponding to   t = duration of fault in seconds
                  a crushed  rock  layer of  thickness,  h, and a   = thermal coefficient of resistivity  at  a
                  reflection factor k                              reference temperature of 20°C
         where                                                pz0 = resistivity  of ground conductor at a
          k=-- '-"                                                 reference temperature of 20°C in p  Q/cm
                   and
              P + P\                                    &)(at 0°C) = reciprocal of
                                                                 = maximum allowable temperature in  "C
                                                             I,,,,
          p = ground resistivity  in Qm                      tamb. = ambient temperature in "C
          p, = crushed rock (gravel) resistivity  in Rm
         Ground resistance
                                                        Actual maximum touch and step voltages of a
         (i) For grid depths up  to 250 mm              grounding station

                                               (22.12)   Max. step voltage, E,(actual)  =  P' K, ' K, ' IC   (22.17)
                                                                                      L
              R,  = station ground resistance in R      and mesh or maximum touch voltage,
              p  = average resistivity  of  soil in Rm
                                                                   p. K,,  . K, .I,
          -  15   ground resistance at the              E, (actual) =    L                   (22.1 X)
          4  ,;A=
                  surface of the ground                 For details refer to the text
              __  = ground resistance  of the total buried
                  length (L) of conductors              Estimating the value of ground conductor length
                                                        to design the grounding grid
         Total length of the buried conductors                 p' K,  . K, .I,  4
                                                        L>                                   (22.19)
          L  = IZ., . b + ilk  a + II..  . h metres   (22.13)   ( I .5 C, . p5 + 1 000) X 0.1 57
                           h
   759   760   761   762   763   764   765   766   767   768   769