Page 110 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 110

S      120 MVA
                         I   I                       5020 A
                          A   L
                                   3  T    3  V    13.8 kV
                                                                   
                 The power factor is 0.8 lagging, so  I   5020  36.87  A .  The phase voltage is 13.8 kV /  3  = 7967
                                                   A
                 V.  Therefore, the internal generated voltage is
                            E   V  R I    jX I
                          A        A A    S A
                             E  7967 0       0.1    5020     36.87   A    j 1.2    5020     36.87   A 
                          A
                                         
                                    
                         E A    12,800 20.7  V
                 The resulting voltage regulation is
                                     
                              12,800 7967
                         VR                 100% 60.7%
                                                  
                                  7967
                 (b)  If the generator is to be operated at 50 Hz with the same armature and field losses as at 60 Hz (so
                 that  the  windings  do  not  overheat),  then  its armature and field currents must not change.  Since the
                 voltage of the generator is directly proportional to  the  speed  of the generator, the voltage rating (and
                 hence the apparent power rating) of the generator will be reduced by a factor of 5/6.

                                5
                                  V     13.8 kV   11.5 kV
                          T ,rated  6
                               5
                                 S      120 MVA   100 MVA
                          rated  6
                 Also, the synchronous reactance will be reduced by a factor of 5/6.

                              5
                           S    X   1.2     1.00 
                              6
                 (c)  At 50 Hz rated conditions, the armature current would be
                                    S      100 MVA
                         I   A  I   L                5020 A
                                   3  T    3  V    11.5 kV

                                                                   
                 The power factor is 0.8 lagging, so  I A   5020 36.87  A .  The phase voltage is 11.5 kV /  3  = 6640
                 V.  Therefore, the internal generated voltage is
                            E   V  R I    jX I
                          A        A A    S A
                             E  6640 0       0.1    5020     36.87   A    j 1.0    5020     36.87   A 
                          A
                                         
                                    
                         E A    10,300 18.8 V
                 The resulting voltage regulation is

                                     
                              10,300 6640
                                                  
                         VR                 100% 55.1%
                                  6640
          Problems 4-16 to 4-26 refer to a six-pole Y-connected synchronous generator rated at 500 kVA, 3.2 kV, 0.9 PF
          lagging, and 60 Hz.  Its armature resistance  R A   is 0.7 .  The core losses of this generator at rated conditions are
          8 kW, and the friction and windage losses are 10 kW.  The open-circuit and short-circuit characteristics are shown
          in Figure P4-2.







                                                           104
   105   106   107   108   109   110   111   112   113   114   115