Page 264 - Introduction to Marine Engineering
P. 264

Fire  fighting  and  safety  239

         The  carbon  dioxide  extinguisher  is tested  to  207 bar  initially  every 10
         years  and  after  two  such  tests,  every  five  years.  The  dry  powder
         extinguisher  is tested  to 35 bar  once  every  four  years.
           Most extinguishers should  be tested  by discharge over a period of one
         to five years, depending on the extinguisher  type, e.g. soda-acid  and dry
         powder  types 20% discharged'per year, foam  types 50% discharged  per
         year. Carbon  dioxide extinguishers should be weighed every six months
         to check'  for  leakage.
           Where   practicable  the  operating  mechanisms  of  portable  extin-
         guishers  should  be examined  every three  months.
           Any plunger should be checked  for free movement, vent holes should
         be  clear  and  cap  threads  lightly  greased.  Most  extinguishers  with
         screw-on caps have a number of holes in the threaded region.  These are
         provided  to release  pressure  before  the cap is taken off: they should be
         checked  to be clear.


         Fixed  installations
         A  variety  of  different  fixed  fire  fighting  installations  exist,  some  of
         which are specifically designed  for  certain  types of  ship. A selection  of
         the  more general  installations will  now be outlined.

         Fire main
         A sea water supply system to fire hydrants is fitted to every ship  (Figure
          13.8). Several pumps in the engine room  will be arranged to supply  the
         system,  their  number  and  capacity  being  dictated  by  legislation
         (Department  of Transport for UK registered vessels). An emergency  fire
         pump   will  also  be  located  remote  from  the  machinery  space  and  with
         independent  means of  power.



                                                Forecastle deck
            Accommodation                       hydrant
            deck hydrants








                                               Booster  _c»Ol
                                               pump I  MJMJ

         Figure  13.8  Fire main