Page 283 - Introduction to Marine Engineering
P. 283

Electrical equipment  257

          A  delay  mechanism  prevents  the  breaker  opening  for  short-period
          overload  currents. The  circuit breaker  opens or  closes both  supply and
          return  leads in the circuit.  Where  a circuit  breaker  feeds the  generator
          supply to the  bus-bars  a third  'make-or-break' arm  will be provided  for
          the equaliser  connection.
            Preferential  tripping  is  a  means  of  retaining  essential  electrical
          supplies.  In  the  event that  a generator cannot  supply all the  load  then
          non-essential loads are disconnected by preferential  trips. The  intention
          is to reduce  the  generator  load  while ensuring  essential equipment such
          as steering gear,  navigation  lights,  etc.,  retains its electrical  supply.
            Various  circuit  faults can  occur  as  a  result  of  either  a  break  in  the
          conductor  (cable)  or  a  break  in  the  insulation.  An  open-circuit  fault
          results from a break in the conductor and  no current flow will take place,
          A  short-circuit  fault  is  due  to  two  breaks  in  the  insulation on,  for
          example, adjacent  conductors.  The  two conductors  are connected  and a
          large current  flow  takes place. An earth  fault occurs when a break in the
          insulation permits the conductor to touch an earthed  metal enclosure (or
          the  hull).
            Earth  faults are usually detected by the use of earth  indicating lamps.
          Two  lamps  are  used,  each  rated  for  the  full  system  voltage,  but
          connected in series across the system with the mid point earthed  (Figure
          14.3),  If  the  system is correctly  insulated then  both  lamps will  glow  at



                                    Bus bars




                    Lamp     Lamp






          Figure  14.3  Earth lamp circuit


          half  brilliance.  The  lamps  are  placed  close  together  to  enable  a
          comparison  to  be  made. A direct earth  in  one  pole  will  short circuit its
          lamp, causing the other to shine brighdy. A slight insulation breakdown
          would  produce  a difference  in bulb brightness between the two. Where
          an  earth  fault  is detected  the  circuit breakers  for  each  separate  circuit
          must  be  opened  in  turn  until  the  fault  location  is  discovered.  The
          particular section or distribution box would then have to have its circuits
          investigated  one  by one  to  locate the  fault  and  enable its correction.
   278   279   280   281   282   283   284   285   286   287   288