258   Electrical equipment

                 Direct current  supply
                 The  supply to a distribution system  will usually come from  two or  more
                 generators operating in parallel.  Each generator must be provided  with
                 certain protective devices to ensure against reverse currents, low voltage
                 or an overcurrent. There must also be ammeters and  voltmeters in the
                 circuits to enable  paralleling to take place.
                   The  circuit for two generators operating  in parallel is shown in Figure
                 14.4. A triple-pole circuit breaker connects the supply to the bus-bars and
                 also  the  equaliser  bus-bar.  The  arrangement  of  the  various  protective
                 trips can be seen, with excess current protection  being provided in each
                 pole.  The  reverse current  trip  prevents  the  generator  operating  as a
                 motor  if, for  instance, the  prime mover stopped.
                   The  voltmeters and  ammeters are  provided  in the  generator  supply
                 circuits  for  paralleling  purposes.  A  voltmeter  is positioned  across  the
                 bus-bars  to  indicate  their  voltage.  Consider  the  situation  where  one


                                                                       Bus  ban


                                                                       Equaliser
                 Ammeter
                  Circuit
                  breaker










                        Series field
                        1
                        —CA-A-T-
                        Shunt field  ,
                                 Resistance
                 Figure  14.4 Protective trips for  the  parallel operation of two d,c. generators

                 generator  is supplying the  bus-bar  system  and  a second  generator  is to
                 be paralleled with it. The  second machine is run  up to speed  and its field
                 current  adjusted  until  the  two machines are  at  the  same  voltage.  The
                 circuit breaker connecting the second machine to the bus-bar can now be
                 closed and  the  Field current adjusted  to enable the generator  to take its
                 share of the  load. When the  load is evenly shared  the  two machines can
                 then  be left  to operate in  parallel.  The  equalising connection  will cater
                 for  any  slight changes in  load  sharing that occur.