Page 149 - Mechanical Engineer's Data Handbook
P. 149

138                                                 MECHANICAL ENGINEER'S DATA  HANDBOOK


                                         2 c







                         Cold fluid
                                    ab
                                                                      4
             Heat transferred q=  UAB,
                                 1
             Overall coefficient u =
                               1
                               -+-  1                    3.15.2   Multi-pass and mixed-flo  w heat
                               ha  hll                   exchangers
             Heat-exchanger effectiveness E =-           In  some  cases  the  values  for  Om for  parallel-  and
                                       lta-  ltb         counter-flow types may be used for these, with reason-
             Note: if  one of the fluids is a wet vapour or a boiling   able accuracy. Otherwise, correction factors must be
             liquid, the temperature is constant  and  ,t = ,t.   used.

             Counter Jlow

             The temperature range possible is greater than for the
             parallel-flow type. The same formulae apply.






                                                                Multi-pass-type heat exchanger









             Cross-Jlo w                                       Mixed-flow-type heat exchanger

             Instead of using 8,  as above, 0°K  is used, where K is a
             factor obtained from tables.                3.15.3   Steam condenser
             q=  UAKO,
                                                         The  steam  condenser  is  a  particular  type  of  heat
               If one fluid is a wet vapour (constant temperature),   exchanger in which one fluid is usually cooling water
             Om  is the same as for parallel-flow and counter-flow   and the other wet steam which condenses on the tubes
             types.                                      carrying the cooling water. It is assumed that the steam
               If 0, and 8, are nearly the same, the arithmetic mean   temperature is constant throughout (Le. at the satura-
             temperature difference is used:             tion  temperature).  Formulae for cooling-water flow
   144   145   146   147   148   149   150   151   152   153   154