692   General-Purpose Control Devices




















                                                             (a)






















                                                             (b)


                            CMD := AUTO_CMD & AUTO_MODE OR MAN_CMD & NOT MAN_CMD_CHECK & NOT

                            AUTO_MODE;
                            CMD_TMR(IN := CMD, PT := T_CMD_MAX);

                            ALRM_FF(S1 := CMD_TMR.Q & NOT FBDK, R := ACK);
                            ALRM := ALRM_FF.Q1;
                                                             (c)
                                        Figure 10 Programmable controller programming example.
   696   697   698   699   700   701   702   703   704   705   706