Page 127 - Offshore Electrical Engineering Manual
P. 127

114    CHAPTER 11  Power Electronics (Semiconductor Equipment)




                            Provided the platform generated frequency and voltage are reasonably stable and
                         within a few percent of the nominal values, the inverter will normally remain in syn-
                         chronism with the generated supply. During generated voltage or frequency excur-
                         sions, the inverter will isolate itself from the main supply and continue to feed the
                         load by itself. A mains bypass supply is also available and, if the inverter fails, it is
                         automatically connected to the load. However, in some designs, if the bypass supply
                         is outside the inverter voltage or frequency tolerance, it will not be made available
                         to the load. This can be a problem if the generated supply is being obtained from the
                         emergency generator, which will not normally have such good voltage or frequency
                         holding capabilities as the larger machines.
                            It should be remembered that the inverter itself is generating a sine wave from
                         a power oscillator and therefore cannot produce a fault current much greater than
                         its rated current. For example, a 20-A inverter with the bypass supply unavailable
                         is able, at best, to blow a 6 A fuse in a reasonable time. If the distribution system
                         requires larger fuses, then an inverter of higher rating will normally be required. It
                         will not be necessary to provide a larger battery, however.




                         SELECTION OF VOLTAGE TOLERANCES
                         The general rule for establishing voltage tolerances is to optimise these for the mini-
                         mum output cable cross-sectional area and battery size. Having been provided with
                         or having calculated the diversified load current, discharge duration and voltage tol-
                         erances required for the equipment being supplied, the engineer can establish the
                         minimum battery size from the manufacturer’s tables.
                            However, this takes no account of the voltage drop in the DC output cable. This
                         voltage drop must be catered for in the supply system to ensure that the lower tol-
                         erance of the supplied equipment is not exceeded, as shown in Table 2.11.1, for a
                         nominal 24 V DC system. The fire and gas panel supply shown in the table requires a
                         150-mm  cable because the voltage drop has been restricted to 0.5 V DC. If the mini-
                                2
                         mum voltage at the charger is raised to 23.1 V DC, it would be possible to reduce the
                                        2
                         cable size to 70 mm . However, to raise this voltage, it would be necessary to increase
                         the battery capacity, assuming the required discharge time remains constant.

                          Table 2.11.1  Voltage Tolerances
                                             Cable       Volts at Charger  Volts at Equipment
                                                 2
                                             (mm /
                          Equipment  Load (A) length)  Min.     Max.      Min.     Max.
                          Fire/gas   40      150/50 m  22.5     26.4      22.0     26.4
                          panel
                          ESD panel  12.5     35/45 m  23.1     27.0      22.5     26.9
                          PA system  25       95/100 m  22.6    26.4      21.6     26.4

                          ESD, emergency shutdown; PA, public address.
   122   123   124   125   126   127   128   129   130   131   132