Page 152 - Offshore Electrical Engineering Manual
P. 152

Cathodic Protection  139




                    2.   Analysis of samples of all materials used for the minimum performance
                     required. Insulation thicknesses should be more generous than those for
                     cables used on land. If screen drain-wires are required, ensure that these
                     do not have a ‘cheese-wire’ effect on insulation when the umbilical is in
                     tension.
                    3.   Close control of conductor and insulation diameter and thickness of each cable
                     during manufacture.
                    4.   Samples of each cable should be taken at the start and finish of each stage of
                     the cable manufacturing run for analysis, and results of analysis known before
                     continuing with the next stage.
                    5.   The final testing of each cable should include insulation resistance, high voltage
                     testing and measurement of total cable resistance, reactance, capacitance and
                     attenuation over a given frequency range. If dc switching or digital signal are
                     being transmitted, low attenuation at MHz frequencies may be important in
                     order to avoid degradation of the signal over the length of the cable. Such read-
                     ings may also detect faults, if attenuation readings for known healthy cables are
                     available for comparison.
                    6.   A sample of the completed cable should undergo high voltage testing in water
                     at the pressure equivalent to at least the maximum depth of water likely in the
                     installed location. The test is carried out using a pressure vessel with a cable
                     gland at each end. The cable sample is passed between the two glands which are
                     then sealed. The vessel is pressurised and the high voltage can then be applied
                     at the cable ends protruding from the glands. Another high voltage test often
                     conducted on a sample is to submerge the sample in a tray of salt water with one
                     exposed conductor in air at either end. A high voltage is then applied between a
                     submerged conductor (or the tray) and the exposed conductor in air. Both of the
                     above tests are carried out to the maximum voltage available or until a voltage
                     breakdown occurs in the sample.
                    7.   Once all the cables have successfully completed their testing, they may be
                     incorporated into the umbilical. However, if there is a delay between cable and
                     umbilical manufacture or the cable has to be transported to a different, further
                     insulation testing will be required immediately prior to umbilical manufacture
                     to ensure that transit or coiling damage has not occurred. It should also be
                     remembered that faults due to poor curing of the (plastic) insulation may appear
                     several weeks after manufacture.




                  CATHODIC PROTECTION
                  INTRODUCTION
                  Cathodic protection provides an effective method of mitigating corrosion damage to
                  subsea metal structures, whether their surfaces are coated or not.
                     Impressed current cathodic protection is preferred for long-term protection of
                  both platform structures and subsea pipelines whereas galvanic or sacrificial anode
   147   148   149   150   151   152   153   154   155   156   157