244 CHAPTER 6 Calculation of Load Flow, Fault Currents
Asymm. (%)
Interrupting Duty (@ Contact Parting Time) Degree of DC Fault Symm. Asymm. Current (kA) kA Peak 117.85 3.016 2.559 3.517 140.81 3.022 2.146 3.382 133.82 2.996 2.239 3.388 58.93 7.188 12.198 58.93 7.446 12.635 58.93 7.358 12.485
Short Circuit Duty Summary Report Generator Circuit Breaker 3-Phase Fault Currents: (Prefault Voltage = 102% of the Bus Nominal Voltage) Momentary Duty (@ 1/2 Cycle) Symm. Asymm. kA rms kA rms kA Peak 1.809 6.803 1.518 6.396 1.583 6.458 11.228 8.625 23.444 11.631 8.935 24.280 11.492 8.828 24.003
Generator Circuit Breaker Evaluation per IEEE C37.013
Symm. Asymm. kA rms kA rms 4.575 1.853 4.472 1.558 4.463 1.628 14.155 8.660 14.660 8.969 14.492 8.867
Source and Generator PF Gen-lagging PF Gen-leading PF Gen-no load Sys-lagging PF Sys-leading PF Sys-no load
Circuit Breaker Type 5 cy Sym CB
ID CB4