Page 305 - Offshore Electrical Engineering Manual
P. 305

292    CHAPTER 2  Electrical System Earthing




                          (A) MAIN CONTROLROOM
                             TO I.S. EARTH BAR IN:   TO NON I.S. EARTH BAR IN:
                                               2
                                                                       2
                             -SCADASYSTEM  MIN 10 MM  CU   -SCADASYSTEM  MIN 10 MM  CU
                                                                       2
                                               2
                             -ESD SYSTEM  MIN 10 MM  CU   -ESD SYSTEM  MIN 10 MM  CU
                                               2
                                                                       2
                             -F&G SYSTEM  MIN 10 MM  CU   -F&G SYSTEM  MIN 10 MM  CU
                                               2
                                                                       2
                                                                 MIN 10 MM  CU
                                          MIN 10 MM  CU
                             -DATA ACO. SYSTEM       -DATA ACO. SYSTEM
                                                   NOTE 3                  NOTE 3
                                                   ISE                     IE
                                                   MAIN INSTRUMENT EARTH BAR  MIE
                                      NOTE 6                          NOTE 3      NOTE 6
                                  TO PLATFORM                                     TO PLATFORM
                                  CENTRAL EARTH                                   CENTRAL EARTH
                                  POINT                                           POINT
                                (B)  FIELD MODULE
                                                 I.S. EARTH BAR  NOTE 3




                                                        JUMPER  ISE                NOTE 7
                                                 NON I.S. EARTH BAR  NOTE 3
                                                                  MODULE
                                                                  MAIN
                                                                  EARTH BAR
                                                                IE
                                                        JUMPER                     NOTE 7
                                                  PE PROTECTION
                                                  EARTH BAR



                                                                PE






                         FIGURE 5.2.2
                         (A) Typical instrument earthing (control Room). Note 3, instrument earth bars to be
                                                                       2
                         mounted on insulators; Note 6, all main earth bars are 70 mm  (B) Typical instrument
                         earthing (field). Note 3, instrument earth bars to be mounted on insulators; Note 6, all
                         main earth bars are 70 mm ; Note 7, protective earth (PE) terminals for components to be
                                             2
                         connected to the main structure by distributed local earth bus. ESD, emergency shutdown;
                         F&G, fire and gas; IS, intrinsically safe; SCADA, supervisory control and data acquisition.