Page 306 - Offshore Electrical Engineering Manual
P. 306

Ships  293




                           PANEL             NOTE 3
                            INDIVIDUAL SCREEN WIRE                      ISE
                                                                         IE

                                                                        PE


                                         NOTE 1
                                                                        PE

                                                                        PRIME STRUCTURE


                   FIELD:


                                              ARMOURED MULTICORE CABLE WITH
                   FIELD JUNCTION BOX:        INDIVIDUAL SCREEN
                             BRASS GLAND
                                              TO STRUCTURE
                                              NON METALLIC BOX      2
                                                                10 MM  CU
                          2
                      2.5 MM  CU              INIVIDUAL SCREEN WIRE
                                   + -  +  -  NOTE 1
                                               BRONZEPLATE
                                                 ISOLATED EARTHING
                                                   TERMINAL ISE
                                                    2
                                                10 MM  CU          EARTH BOSS WELDEO
                   FIELD INSTRUMENT:                               TO STRUCTURE

                      METALLIC BOX WITH       NON METALLIC BOX     STRUCTURE
                      EARTH STUD              WITH EARTH TAG
                                                ISOLATED SCREEN


                                   TYPICAL IS CIRCUIT

                  FIGURE 5.2.3
                  Typical instrument panel intrinsically safe (IS) earthing. Note 1, if the enclosure is made
                  from metal <3 mm, a glandplate of minimum thickness 3 mm is to be provided; Note 3, IS
                  instrument and electrical earth bars to be provided with linking bars. Instrument bar to be
                  mounted on insulators.
   301   302   303   304   305   306   307   308   309   310   311