64     CHAPTER 4  Prime Mover Selection Criteria




                                                               100 PO
                                             40 OHMS
                                             100 A for 30 sec
                                             4A continuous
                                                   101

                                                               Protection and
                                                               instrumentation
                                          2.6 MW 3.25 MVA
                                          0.8 PF X’d = 15%

                                                   102






                                                               Protection and
                                                               instrumentation



                                                    630 A
                                                     E
                                                             EB
                                                      SYN   EC        1250 A
                                                   L2
                                                          L1          S
                                                     EC                SYN
                         FIGURE 2.4.4
                         Medium-voltage resistance earthed arrangement.




                         it became necessary to fly a small generator set or compressor out to the plat-
                         form in order to restart generators and hence continue the output of oil from the
                         installation.
                            Maintenance must also be catered for in starting facilities such that whilst part of
                         the system is being maintained, there is still at least one method of black start open to
                         the operator. An example of this would be the need to allow for planned or unplanned
                         outages in the emergency switchboard whilst still providing electrical supplies to
                         main generator facilities, such as engine cranking motors and lube oil auxiliaries; a
                         provision which has often been overlooked in the past.