Disconnecting Switches and Earthing Switches Chapter | 12  139


                The results at site shown in Fig. 12.8 was in the range of 45 50 μΩ.
             4. Insulation test
                a. This can be done by Megger tester at 5000 V DC.
             5. High voltage AC test
                a. This test will be done during the first energization of the substation
                   with a nominal voltage of the disconnecting switch.