Page 143 - Practical Power System and Protective Relays Commissioning
P. 143

142  Practical Power System and Protective Relays Commissioning
























            FIGURE 13.1 Fault recorder unit setup.

            13.2 FAULT RECORDER TESTING

            These tests include the following:
            1. Adjusting the prefault, fault, and postfault times on the fault recorder
               units and check that they are working correctly for a simulated fault by
               secondary injection. Check the operation of both the analog channels and
               the digital channels.
            2. Check that all points of analog channels and digital channels are trans-
               ferred to the local and remote annunciator inside the substation.
            3. Check that all points of analog channels and digital channels are trans-
               ferred to the National Control Center SCADA system.