Page 240 - Practical Power System and Protective Relays Commissioning
P. 240
238 Practical Power System and Protective Relays Commissioning
FIGURE 18.7.2 Overall differential scheme for generator units.
18.7.3 STATOR EARTH FAULT PROTECTION (100%)
This scheme is applied for large machines only.
A low-frequency injection method is shown in Fig. 18.7.4:
Complete protection for stator windings;
High cost of injection equipment is a disadvantage.
Third harmonic neutral voltage scheme as shown in Fig. 18.7.5:
27 Third harmonic undervoltage relay;
59P terminal voltage check permits for trip if circuit breaker is open but
a terminal voltage is present;
Neutral overvoltage protection operates at a fundamental frequency
voltage of 50 Hz.
The trip logic is shown in Fig. 18.7.6.
As shown in Fig. 18.7.7, the overlapping of the operation of fundamental
frequency overvoltage relay-59 and the third harmonic undervoltage relay-27
will cover by 100% the protection for the stator.