238  Practical Power System and Protective Relays Commissioning

































            FIGURE 18.7.2 Overall differential scheme for generator units.


            18.7.3 STATOR EARTH FAULT PROTECTION (100%)
            This scheme is applied for large machines only.
               A low-frequency injection method is shown in Fig. 18.7.4:
               Complete protection for stator windings;
               High cost of injection equipment is a disadvantage.

               Third harmonic neutral voltage scheme as shown in Fig. 18.7.5:
               27 Third harmonic undervoltage relay;
               59P terminal voltage check permits for trip if circuit breaker is open but
               a terminal voltage is present;
               Neutral overvoltage protection operates at a fundamental frequency
               voltage of 50 Hz.
               The trip logic is shown in Fig. 18.7.6.
               As shown in Fig. 18.7.7, the overlapping of the operation of fundamental
            frequency overvoltage relay-59 and the third harmonic undervoltage relay-27
            will cover by 100% the protection for the stator.