Page 245 - Practical Power System and Protective Relays Commissioning
P. 245

242  Practical Power System and Protective Relays Commissioning


            18.7.5 OVERCURRENT PROTECTION
            This protection is the only protection for small units. It provides protection
            for the generator and power system, therefore a time delay is required for
            coordination.
               Refer to Fig. 18.7.9 for the OC protection.




















            FIGURE 18.7.9 OC protection for generators.

               The variable response of a generator for change in excitation and voltage
            regulation led to use of overcurrent relays with different characteristics based
            on the generator terminal voltage value.
               There are two types of OC protection applied to generators:
               1. Voltage-controlled overcurrent protection
               During normal overloads, system voltage is near normal and the relay
            operates on long inverse time characteristics but under close-up fault condi-
            tions the busbar voltage falls and the voltage relay will change the relay
            characteristics to standard IDMT characteristics. Refer to Fig. 18.7.10 for
            voltage control overcurrent relay.
               2. Voltage-restrained overcurrent protection
               In this type of relay, the relay characteristic is modified continuously
            based on the generator terminal voltage. Refer to Fig. 18.7.11 for voltage-
            restrained overcurrent protection.



            18.7.6 BACKUP DISTANCE PROTECTION
            This impedance relay is used to provide backup protection for faults on a
            power system which is not cleared by the power system protection. This
            protection operates to trip generators after a time delay, as shown in
            Fig. 18.7.12.
   240   241   242   243   244   245   246   247   248   249   250