246  Practical Power System and Protective Relays Commissioning





























            FIGURE 18.7.14 Out-of-step relay characteristic for generators.

            18.7.10 NEGATIVE-PHASE SEQUENCE CURRENT I 2
            PROTECTION

            Unbalanced loading of generators which generates negative-sequence cur-
            rents in the stator which cause a controlled-rotating magnetic field which
            cuts the rotor at twice the synchronous speed inducing double-frequency cur-
            rent in the field system and rotor body, which leads to eddy currents causing
            overheating, there are two ratings for I 2 for machines as follows:
               I 2 R 5 continuous Negative Phase Sequence (NPS) rating;
                2
               I 2 t 5 short time NPS rating.


            18.7.11 ROTOR EARTH FAULT PROTECTION

            A single fault will not cause any problem but a second fault in the field
            winding of the rotor could cause serious damage including:
               Heating-conductor burning;
               Flux distortion in the field leading to generator vibrations.
               A DC injection method is used by injecting a DC voltage into field wind-
            ings to detect the earth faults, as shown in Fig. 18.7.15.