INDOOR LIGHTING COMPLIANCE  159










































               B
                 Figure 6.10  (Continued )




                  As a rule, allowed lighting power for a building is determined by one of the fol-
               lowing five methods:

               1 Complete building method. This method applies to situations when the entire build-
                  ing’s lighting system is designed and permitted at one time. This means that at least
                  90 percent of the building has a single primary type of use, such as retail. In the case
                  of wholesale stores, at least 70 percent of the building area must be used for mer-
                  chandise sales functions. In some instances this method may be used for an entire
                  tenant space in a multitenant building where a single lighting power value governs
                  the entire building.
               2 Area category method. This method is applicable for any permit situation, includ-
                  ing tenant improvements. Lighting power values are assigned to each of the major
                  function areas of a building, such as offices, lobbies, and corridors.
               3 Tailored method. This method is applicable when additional flexibility is needed to
                  accommodate special task lighting needs in specific task areas. Lighting power