                                             BUILDING CODES, LOADS, AND FIRE PROTECTION*


                                                                   BUILDING CODES, LOADS, AND FIRE PROTECTION  4.35

                                           2400                                              1315.6

                                           2200                                              1204.4


                                           2000                                              1093.3


                                           1800                                              982.2

                                           1600                                              871.1


                                           1400                                              760.0
                                          Degrees F  1200                                    645.9  Degrees C




                                           1000                                              537.8


                                            800                                              426.7

                                            600                                              315.6

                                            400                                              204.4


                                            200                                              93.3


                                                                                             −17.8
                                               0    1     2     3    4     5     6    7     8
                                                                    Hours
                                        FIGURE 4.7  Variation of temperature with time in the standard fire test specified in ASTM E119.
                                        (Source: American Society for Testing and Materials, Conshohocken, Pa., with permission.)



                                  the “standard fire.” Thus fire-resistance requirements are expressed in terms of hours. The design of
                                  free-resistant buildings is typically accomplished in a prescriptive fashion by selecting tested
                                  “designs” that meet specific building code requirements.
                                    It is emphasized that ASTM E119-based fire-resistance ratings are comparative in nature.
                                  They are conducted on idealized laboratory specimens and are not intended to be a predictor of
                                  structural performance of actual buildings in real fires. Special nonstandard fire tests may be
                                  desirable in some cases.
                                    Listings of fire-resistance ratings for construction assemblies are available from a number of sources:

                                  • Fire-Resistance Directory, Underwriters Laboratories, Northbrook, Ill.
                                  • Fire-Resistance Ratings, American Insurance Services Group, New York, N.Y.
                                  • Fire-Resistance Design Manual, Gypsum Association, Washington, D.C.